First, the power switch, usually there are four places in the air shower room to cut off the power:
1. The power switch of the air shower outdoor box.
2. The control panel of the air shower indoor box.
4. On the outer boxes on both sides of the air shower (the power switch here can prevent the power from being cut off in an emergency, and effectively improve our personal safety). When the power indicator light fails, it is not necessary to re-check the power supply of the above four air showers.
2. When the fan in the air shower is not working, check whether the emergency switch of the outdoor box of the air shower is cut off at the first time.
3. If the fan in the air shower room is reversed or the wind speed in the air shower room is very small, please be sure to check whether the 380V three-phase four-wire line is reversely connected. Generally, a special electrician will connect the line during the factory installation; The light source will cause the fan in the air shower to not work or the wind speed of the reverse air shower will decrease, and the severe case will burn the circuit board of the entire air shower; we should not change the wiring lightly.
4. The air shower room does not blow shower. In addition to the above three points, it is also necessary to check whether the emergency stop button inside the air shower room is pressed. For example, when the emergency stop button is color, the air shower room will not blow shower; To press the emergency stop button again, it can work normally.
5. When the air shower room cannot automatically sense the shower, check the light sensor system in the lower right corner of the box in the air shower to see if the light sensor device is installed correctly. .
6. When the wind speed of the air shower room is very low for a period of time, please check whether the initial and high-efficiency filters of the air shower room have too much dust, and if so, please replace the filter. (The primary filter in the air shower is generally replaced once within 1-6 months, and the high-efficiency filter in the air shower is generally replaced once within 6-12 months)